Inspect an AHU assembly, work through duct-sizing arithmetic in SI and IP units, and trace the result onto a detailed 2D design study.

AHU-01 / EQUIPMENT STUDY

The engineering inside an air-handling unit.

Follow the air through a detailed draw-through cooling unit.

01 / ENTERING AIR26.0°C 78.8°F

Before the cooling coil

02 / LEAVING COIL13.0°C 55.4°F

Heat removed at the coil

03 / SUPPLY AIR13.5°C 56.3°F

Includes +0.5°C fan heat

AHU / FUNCTIONAL SEQUENCE

Inlet damper → filter bank → cooling coil → draw-through fan → supply duct

The calculation and drawing below remain available without the 3D view.
SERVICE-SIDE CUTAWAYEntering airCooled airIllustrative airflow
01Inlet controlOpposed blades regulate the entering air path.
02FiltrationPleated cassettes with differential-pressure monitoring.
03Cooling coilAir loses heat across fins and chilled-water tubes.
04Fan sectionAxial inlet, radial discharge into the fan plenum.
05DischargeConditioned air leaves through the duct transition.

Illustrative cooling example: the coil reduces air temperature; the downstream fan adds 0.5°C (0.9°F). Temperatures and airflow paths explain the process, not a selected duty or CFD result. Dehumidification depends on the air dew point and coil surface temperature.

CALCULATION STUDY / RECTANGULAR DUCT

One calculation.
Both unit systems.

Change airflow and the clear internal duct dimensions. Velocity, SI/IP equivalents and drawing annotations update from the same unrounded values.

Input units
SI / METRIC

5.000m/s

Mean air velocity at section A–A

Volume flow, Q
2.4000 m³/s
Clear area, A
0.4800 m²
v = Q / (W × H)

2.4000 ÷ 0.4800
= 5.000 m/s

IP / INCH–POUND

984.3ft/min

Same velocity, converted units

Volume flow, Q
5,085.3 CFM
Clear area, A
5.1667 ft²
v = 144 × Q / (W × H)

Q in CFM; W and H in inches.
5,085.3 ÷ 5.1667 = 984.3 ft/min

Continuity check: Q = A × v

This checks mean velocity in the selected section. It does not select the fan or validate friction loss, noise, pressure class, leakage or fittings.

1 in = 25.4 mm · 1 ft = 0.3048 m · CFM means ft³/min. Display values are rounded; calculations are not.
2D DESIGN DOCUMENTATION

A drawing that follows the calculation.

DESIGN STUDY / NOT FOR CONSTRUCTION
Supply-air distribution plan and section A–AAn illustrative constant-section main duct serves three equal-flow terminals. Section A–A is before the first branch. Duct section proportions and all selected dimensions and flows update with the calculator. Branch sizes and damper settings are not selected. 1234ABC SUPPLY AIR / DISTRIBUTION STUDYM-101 · CONSTANT-SECTION MAIN · EQUAL TERMINAL FLOW ASSUMPTION ZONE 01ZONE 03ZONE 02 AHU-01SYMBOLIC CONNECTION AA 800.0 L/s1,695.1 CFM800.0 L/s1,695.1 CFM 800.0 L/s1,695.1 CFM 2,400.0 L/s5,085.3 CFM 1,600.0 L/s800.0 L/s 800.0 × 600.0 mm31.496 × 23.622 in SECTION A–ABEFORE THE FIRST BRANCHCLEAR INTERNAL DIMENSIONS 800.0 mm / 31.496 in 600.0 mm / 23.622 in Section proportions follow the selected W:H ratio. DESIGN NOTES01 Main duct carries Q at A–A, then 2Q/3 and Q/3 after take-offs.02 Branch dimensions, balancing settings and terminal duties are not selected.03 Plan is schematic / NTS. Sizes are clear air-path dimensions. AUGMINTECHMEP DESIGN & 2D DRAFTINGDRAWINGM-101 / REV 01STATUS / SCALESTUDY / NTS
SD symbols represent supply terminals. Diagonal branch symbols represent balancing dampers.Scroll the sheet to inspect details on smaller screens.
Calculation basis & equipment illustration notes

The worksheet uses continuity, v = Q/A, with the clear rectangular area A = W × H. IP conversions use the exact international foot and inch definitions in NIST SP 811. Converted dimensions are exact equivalents before display rounding, not rounded nominal duct sizes.

The AHU is an explanatory assembly. It is not tied to the selected duct duty and does not claim a verified fan, coil or water-side selection. Actual equipment configuration and installation details must be checked against the selected manufacturer’s documentation. Manufacturer equipment reference.

01 / HVAC CALCULATIONS

Loads. Flows. Duties.

Heat loads, duct sizing, external static pressure and pump head.

2D output: HVAC plans, sections & details
02 / PLUMBING CALCULATIONS

Demand. Storage. Head.

Water demand, pipe sizes, storage requirements and pump selection.

2D output: supply, drainage & riser drawings
03 / FIRE FIGHTING DESIGN

Criteria. Hydraulics. Duty.

Hazard-based inputs, hydraulic calculations and fire-pump duties.

2D output: system layouts & riser drawings
04 / ELECTRICAL CALCULATIONS

Loads. Lighting. Cables.

Lighting levels, load demand, cable selection and voltage drop.

2D output: lighting, power & single-line drawings